Application :
Suitable for wiring in all kind of infrastructure, residential as well as industrial.
Mail Us : info@falgunitrading.in
Suitable for wiring in all kind of infrastructure, residential as well as industrial.
Up to and including 1100 V
IS 694:2010
The conductors, drawn from bright electrolytic grade copper are annealed and bunched together for exibility. rating value and dimensions.
These wires are insulated with a Flame Retardant (FR) PVC.
Red, Yellow, Blue, Black, Green, Gray, White, Any specialized as per customer requirement.
90 Mtr. Coil in Carton Packing, 180 Mtr. Project Coil
| Nominal Area of Conductor | Number/Nom.Dia of wires* (Nom.) | Thickness of Insulation (Nom.) | Overall Diameter (Max) | Current Carrying Capacity* | Resistance(Max) Km.@20°C | |
|---|---|---|---|---|---|---|
| Casing | Concealed | |||||
| Sq,mm | Number/mm | mm | mm | Amps | Amps | Ohm/Km |
| 1.0 | 14/0.30 | 0.7 | 2.8 | 12 | 11 | 18.10 |
| 1.5 | 22/0.30 | 0.7 | 3.1 | 16 | 13 | 12.10 |
| 2.5 | 36/0.30 | 0.8 | 3.8 | 22 | 18 | 7.41 |
| 4.0 | 56/0.30 | 0.8 | 4.4 | 29 | 24 | 4.95 |
| 6.0 | 84/0.30 | 0.8 | 5.2 | 37 | 31 | 3.30 |
* As per IS 3961 (PartV)-1968 and conductor as per IS-8130:1984
| FR Properties | ||
|---|---|---|
| Test | Specification | Value |
| Critical Oxygen Index | ASTM-D 2863 | Minimum 29 |
| Temperature Index | ASTM-D 2863 | Minimum 250ºC |